Run 04 equipment mass balance
Run identity: R4-RECONSTRUCTION-01. Quantity snapshot: SNAP-RUN03. Configuration: CFG-GB300-2026Q4.
All quantities are metric tonnes per canonical 1 GW of commissioned IT. The base design covers incremental B1 compute, B2 facility equipment, and modeled B3 enabling equipment. B1–B3 sums those increments once. Low, base, and high are coherent input constructions with fixed equipment counts. Other feasible designs could fall outside their range. Transfer from retained product and geometry proxies to the target campus is assumption-dependent. The results are scenario estimates with partial campus coverage.
Elemental lithium is a nested view of host compounds. Aggregate ferrous includes disjoint ferrous classes. Summing every material label would count some stock twice.
Cumulative modeled equipment stocks (B1–B3)
| Material | Low (t) | Base (t) | High (t) |
|---|---|---|---|
| Copper-grade stock | 8,718.1 | 16,921.4 | 30,102.3 |
| Aluminum stock and named alloys | 1,565.3 | 2,478.1 | 3,862.6 |
| Disjoint ferrous, linked total | 32,715.7 | 44,281.5 | 59,874.2 |
| Elemental lithium, nested view | 22.6 | 24.0 | 25.9 |
Largest equipment contributors in the base case
Component stocks are summed per equipment population. Ferrous combines the disjoint ferrous classes.
| Stock | Boundary | Equipment population | Base (t) |
|---|---|---|---|
| Copper | B3 | R4-FEEDER-GENERATOR | 4,152.7 |
| Copper | B2 | R4-FEEDER-IT-OUTPUT | 1,741.0 |
| Copper | B2 | R4-FEEDER-IT-RECTIFIER | 1,417.1 |
| Copper | B2 | R4-FEEDER-IT-XFMR | 1,384.2 |
| Copper | B2 | R15-BOM-AIR-COOLED-CHILLER | 1,041.4 |
| Aluminum | B2 | R15-BOM-AIR-COOLED-CHILLER | 1,154.6 |
| Aluminum | B3 | R15-BOM-STANDBY-GENERATOR | 346.7 |
| Aluminum | B2 | R15-BOM-WARM-WATER-CRAH | 346.6 |
| Aluminum | B2 | R15-BOM-IT-UPS | 265.8 |
| Aluminum | B1 | R4-PSU-MODULE | 127.5 |
| Ferrous | B3 | R15-BOM-STANDBY-GENERATOR | 8,240.0 |
| Ferrous | B2 | R15-BOM-IT-XFMR | 5,468.2 |
| Ferrous | B2 | R15-BOM-AIR-COOLED-CHILLER | 5,451.2 |
| Ferrous | B2 | R15-BOM-PDU | 5,342.3 |
| Ferrous | B2 | R15-BOM-PRIMARY-PIPE-RUN | 4,617.5 |
Historical reconciliation
The comparison table presents previously reported quantities alongside the current model results. Model development coefficients and ledger quantities are evaluated independently of that table. Agreement here uses historical display precision. The archived report's marginal material endpoints and the modeled joint cases have different uncertainty semantics.
Across low, base, and high, 19 endpoints agree at historical display precision, 128 differ, and 6 lack a value on one or both sides.
Delta is modeled minus historical. Missing estimates are shown as —. The CSV and JSON include all endpoints and historical display tolerances.
| Boundary | Material | Modeled base (t) | Historical base (t) | Delta (t) |
|---|---|---|---|---|
| B1 | aluminum | 213.26 | 290 | -76.74 |
| B1 | carbon_steel | 2,377.45 | 2,410 | -32.55 |
| B1 | copper | 1,194.93 | 1,420 | -225.07 |
| B1 | ferrous | 2,575.31 | 2,690 | -114.69 |
| B1 | stainless_steel | 197.86 | 280 | -82.14 |
| B2 | aluminum | 1,910.9 | 3,620 | -1,709.1 |
| B2 | carbon_steel | 13,520.48 | 24,920 | -11,399.52 |
| B2 | cast_iron | 1,725.7 | 2,410 | -684.3 |
| B2 | copper | 10,379.86 | 17,320 | -6,940.14 |
| B2 | electrical_steel | 11,946.57 | 8,060 | 3,886.57 |
| B2 | electrolyte_solvents | 252.01 | 271.8 | -19.79 |
| B2 | ethylene_glycol | 5,462.2 | 6,180 | -717.8 |
| B2 | ferrous | 29,881.4 | 39,710 | -9,828.6 |
| B2 | graphite | 239.63 | 258.5 | -18.87 |
| B2 | lfp | 507.02 | 546.9 | -39.88 |
| B2 | lipf6 | 37.69 | 40.7 | -3.01 |
| B2 | lithium | 24.03 | 25.9 | -1.87 |
| B2 | nickel | 22.13 | 23.9 | -1.77 |
| B2 | other_ferrous | 441.02 | 730 | -288.98 |
| B2 | polyethylene | 81.94 | — | — |
| B2 | r513a | 180.83 | 180.8 | 0.03 |
| B2 | stainless_steel | 2,247.64 | 3,590 | -1,342.36 |
| B2 | transformer_oil | 1,396.35 | 2,470 | -1,073.65 |
| B2 | water | 13,550.28 | 15,350 | -1,799.72 |
| B3 | aluminum | 353.97 | 310 | 43.97 |
| B3 | carbon_steel | 4,008.8 | 9,090 | -5,081.2 |
| B3 | cast_iron | 4,067.71 | 4,720 | -652.29 |
| B3 | copper | 5,346.63 | 5,720 | -373.37 |
| B3 | electrical_steel | 3,601.31 | 4,600 | -998.69 |
| B3 | ferrous | 11,824.83 | 18,480 | -6,655.17 |
| B3 | other_ferrous | 147 | 80 | 67 |
| B3 | transformer_oil | 647.28 | 730 | -82.72 |
| B1-B3 | aluminum | 2,478.13 | 4,220 | -1,741.87 |
| B1-B3 | carbon_steel | 19,906.73 | 36,420 | -16,513.27 |
| B1-B3 | cast_iron | 5,793.41 | 7,130 | -1,336.59 |
| B1-B3 | copper | 16,921.42 | 24,470 | -7,548.58 |
| B1-B3 | electrical_steel | 15,547.88 | 12,660 | 2,887.88 |
| B1-B3 | electrolyte_solvents | 252.01 | 271.8 | -19.79 |
| B1-B3 | ethylene_glycol | 5,462.2 | 6,180 | -717.8 |
| B1-B3 | ferrous | 44,281.54 | 60,880 | -16,598.46 |
| B1-B3 | graphite | 239.63 | 258.5 | -18.87 |
| B1-B3 | lfp | 507.02 | 546.9 | -39.88 |
| B1-B3 | lipf6 | 37.69 | 40.7 | -3.01 |
| B1-B3 | lithium | 24.03 | 25.9 | -1.87 |
| B1-B3 | nickel | 22.13 | 23.9 | -1.77 |
| B1-B3 | other_ferrous | 588.02 | 800 | -211.98 |
| B1-B3 | polyethylene | 81.94 | — | — |
| B1-B3 | r513a | 180.83 | 180.8 | 0.03 |
| B1-B3 | stainless_steel | 2,445.5 | 3,870 | -1,424.5 |
| B1-B3 | transformer_oil | 2,043.63 | 3,200 | -1,156.37 |
| B1-B3 | water | 13,550.28 | 15,350 | -1,799.72 |
The table compares labels and published scope. Differences include effects of component coverage, assumed dimensions, product transfer, and case definitions. The archived material envelopes do not supply the calculation inputs needed to attribute a difference to any one coefficient.
- B1–B3 ferrous base differs by -16,598.46 t (-27.3% of the historical base). The largest incremental difference is B2 (-9,828.6 t).
- B1–B3 carbon steel base differs by -16,513.27 t (-45.3% of the historical base). The largest incremental difference is B2 (-11,399.52 t).
- B1–B3 copper base differs by -7,548.58 t (-30.8% of the historical base). The largest incremental difference is B2 (-6,940.14 t).
Replacement designs and gaps
Replacement cases in the modeled balance apply to the named assemblies. The historical alternative deltas are carried in the reconciliation as reported claims with their own scope.
| Replacement | B1–B3 copper Δ (t) | B1–B3 aluminum Δ (t) | B1–B3 ferrous Δ (t) |
|---|---|---|---|
| AL-MV-LV-WINDINGS | -589.89 | 295.61 | 0 |
| AL800-BUSWAY | -589.15 | 214.72 | 0 |
| AL-PHASE-FEEDERS | -10,613.89 | 5,318.88 | 0 |
| PIPE-HEAVY-WALL | 0 | 0 | 2,625.65 |
The coverage register lists 50 modeled scopes and 11 gap records. Gaps remain outside the quantified sum. See coverage.json for ledger links, physical per-unit masses, budget residuals, missing inputs, and scope notes.
Read budget residuals as accounting constraints and keep them out of the stock totals. The low and high battery module and cabinet budget endpoints are marginal envelopes. Adding those endpoints does not yield a joint 590 kg partition. Modeled battery stock passes the shared 590 kg gross-budget check.
Installed conductor routes and sections, equipment-specific transformer drawings and masses, and selected cooling and battery equipment bills of materials would constrain high-volume metal and chemical-stock estimates. Building shells, foundations, roads, earthworks, and unallocated offsite infrastructure are outside this equipment scope.
Run python scripts/reproduce_run04.py to regenerate these findings and the supporting tables offline. The manifest records SHA-256 hashes of inputs and outputs. The preservation audit compares frozen file bytes with the Run 03 Git tree.
Source details
Run 04 research. Equipment material estimates with documented assumptions and scope. Web prose uses current site terminology; downloadable records preserve original wording. Hashes identify the downloadable records.
Source: build/run04/findings.md
SHA-256: 530ecae0bf37514e35c1f93060f83e7ee534c6582a79e41c7ef70cfc68778607
Download research file
Optional: tell Sid you’re reading
The document is open; sharing your name/email is optional.