"gaps": [
{
"equipment_id": "R15-BOM-CAMPUS-SUBSTATION",
"reason": "Parent/aggregation only. Transformer, MV panels and modeled cooling/power rows are lower-level stocks. Bare HV outdoor bus, surge arresters, supports and fencing unresolved."
},
{
"equipment_id": "R15-BOM-HV-RING-BREAKER",
"reason": "Specific 230 kV breaker and conductor construction unresolved."
},
{
"equipment_id": "R15-BOM-GENERATOR-FUEL-SYSTEM",
"reason": "External fuel tanks, pumps, supply/return piping and initial fuel inventory unresolved."
},
{
"equipment_id": "R15-BOM-WATER-TREATMENT-SKID",
"reason": "Configuration, filter/resin stock, construction and initial fill unresolved."
},
{
"equipment_id": "R15-BOM-COLD-PLATE-ASSEMBLY",
"reason": "Coldplate copper plate and tubing nested in compute-tray calculation. Separate coldplate assembly total would overlap. Remaining coldplate fittings and coolant unresolved."
},
{
"equipment_id": "R15-BOM-BUILDING-STRUCTURE",
"reason": "Building shells, foundations, roads, earthworks and broader civil works excluded."
},
{
"equipment_id": "R4-UNALLOCATED-UTILITY",
"reason": "Upstream generation, offsite transmission/network reinforcement and utility stock allocation unresolved."
},
{
"equipment_id": "R4-B1-OTHER",
"reason": "Non-bulk B1 electronics, semiconductors, packages, PCBs, network cabling and optics, electronics reserves, polymers and secondary fittings unquantified."
},
{
"equipment_id": "R4-EXTERNAL-ELECTRICAL",
"reason": "Selected conductor routes are partial. Cable tray thickness and fill, sheath, terminations, cable insulation, grounding, neutrals, raceways, PDU secondary drops to busway, and protected cooling terminal branches remain unresolved."
},
{
"equipment_id": "R4-INTERNAL-FLUIDS",
"reason": "Chiller, CDU, UPS, B1 rack and genset internal operating fluids except the explicit R513A charge remain unquantified. Balances do not represent withdrawals or consumption."
},
{
"equipment_id": "R4-ASSEMBLY-RESIDUALS",
"reason": "Each assembly covers only the listed material-bearing components. Assemblies without comparable gross have unknown residuals. Remaining chemical and metallurgical constituents unquantified."
}
],
"modeled": [
{
"boundary": "B1",
"budget_residual_kg_per_unit": {
"180 kg comparison frame only": {
"base": 25.51200000000003,
"high": 6.907499999999999,
"low": 50.474999999999994
}
},
"equipment_id": "R4-RACK-FRAME",
"ledger_id": "S-RACKS",
"physical_kg_per_unit": {
"base": 154.48799999999997,
"high": 173.0925,
"low": 129.525
},
"quantity": 6785.714285714285,
"scope": "Bare frame, structural members and panels; no busbars, coolant or equipment.",
"thermal_screen": null
},
{
"boundary": "B1",
"budget_residual_kg_per_unit": {
"two typical reference busbars": {
"base": 17.282024654681756,
"high": 17.282024654681756,
"low": 17.282024654681756
}
},
"equipment_id": "R4-RACK-BUSBAR",
"ledger_id": "S-RACKS",
"physical_kg_per_unit": {
"base": 44.717975345318244,
"high": 44.717975345318244,
"low": 44.717975345318244
},
"quantity": 6785.714285714285,
"scope": "Two 1,400 A reference power/return assemblies at 54 V give 151.2 kW nominal per rack; shares, transients, busbar covers and ground arrangement unresolved.",
"thermal_screen": null
},
{
"boundary": "B1",
"budget_residual_kg_per_unit": {},
"equipment_id": "R4-RACK-MANIFOLD",
"ledger_id": "S-RACKS",
"physical_kg_per_unit": {
"base": 15.8635750500194,
"high": 15.8635750500194,
"low": 15.8635750500194
},
"quantity": 6785.714285714285,
"scope": "Dry supply and return main bodies; no rack fluid or fittings.",
"thermal_screen": null
},
{
"boundary": "B1",
"budget_residual_kg_per_unit": {
"comparison Lenovo complete tray": {
"base": 18.43497695222179,
"high": 11.570516721465623,
"low": 23.1119399357821
},
"supplier nested coldplate module": {
"base": 5.395826952221787,
"high": 2.6754167214656244,
"low": 7.4360899357821
}
},
"equipment_id": "R4-COMPUTE-TRAY",
"ledger_id": "S-TRAYS",
"physical_kg_per_unit": {
"base": 10.565023047778213,
"high": 17.429483278534377,
"low": 5.8880600642179
},
"quantity": 122142.85714285713,
"scope": "Compute tray with nested four GPU and two CPU cold plates, coldplate tubes and wiring. Electronics and fittings unresolved.",
"thermal_screen": null
},
{
"boundary": "B1",
"budget_residual_kg_per_unit": {
"comparison Lenovo switch tray": {
"base": 9.345064097097275,
"high": 3.7051040328793725,
"low": 13.19832726624708
}
},
"equipment_id": "R4-SWITCH-TRAY",
"ledger_id": "S-NV",
"physical_kg_per_unit": {
"base": 7.654935902902725,
"high": 13.294895967120627,
"low": 3.801672733752919
},
"quantity": 61071.428571428565,
"scope": "NVLink switch sheet chassis and thermal stack; no external cartridges or data cables.",
"thermal_screen": null
},
{
"boundary": "B1",
"budget_residual_kg_per_unit": {},
"equipment_id": "R4-POWER-SHELF-BARE",
"ledger_id": "R1-E-SHELVES",
"physical_kg_per_unit": {
"base": 6.035950000000001,
"high": 9.842699999999999,
"low": 3.2809
},
"quantity": 54285.71428571428,
"scope": "Bare power shelf enclosure and internal bus. Removable PSUs counted in own ledger row.",
"thermal_screen": null
},
{
"boundary": "B1",
"budget_residual_kg_per_unit": {},
"equipment_id": "R4-PSU-MODULE",
"ledger_id": "R1-E-PSUS",
"physical_kg_per_unit": {
"base": 1.3462500000000002,
"high": 2.30985,
"low": 0.7130000000000001
},
"quantity": 325714.2857142857,
"scope": "Removable PSU gross unknown; thermal aluminum, sheet enclosure and conductors estimated independently.",
"thermal_screen": null
},
{
"boundary": "B3",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-HV-XFMR",
"ledger_id": "R15-HV-XFMR-COUNT",
"physical_kg_per_unit": {
"base": 147177.52800097378,
"high": 176727.6796368346,
"low": 120722.78759183394
},
"quantity": 24,
"scope": "Separate three-limb core, windings, tank/cabinet and where applicable liquid fill. PDU includes at most one transformer. Cooling attachments and other transformer hardware unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-IT-XFMR",
"ledger_id": "R15-IT-XFMR-COUNT",
"physical_kg_per_unit": {
"base": 16120.412133945365,
"high": 19266.832174301187,
"low": 13235.805642808107
},
"quantity": 428,
"scope": "Separate three-limb core, windings, tank/cabinet and where applicable liquid fill. PDU includes at most one transformer. Cooling attachments and other transformer hardware unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-FAC-XFMR",
"ledger_id": "R15-FAC-XFMR-COUNT",
"physical_kg_per_unit": {
"base": 11978.823573676487,
"high": 14066.372481110895,
"low": 9827.820941089592
},
"quantity": 214,
"scope": "Separate three-limb core, windings, tank/cabinet and where applicable liquid fill. PDU includes at most one transformer. Cooling attachments and other transformer hardware unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {
"matched functional PDU proxy": {
"base": 1107.8065813426924,
"high": 569.1104853725205,
"low": 1669.9768294123664
}
},
"equipment_id": "R15-BOM-PDU",
"ledger_id": "R15-PDU-COUNT",
"physical_kg_per_unit": {
"base": 3442.1934186573076,
"high": 3980.8895146274795,
"low": 2880.0231705876336
},
"quantity": 1712,
"scope": "Separate three-limb core, windings, tank/cabinet and where applicable liquid fill. PDU includes at most one transformer. Cooling attachments and other transformer hardware unresolved.",
"thermal_screen": null
},
{
"boundary": "B3",
"budget_residual_kg_per_unit": {
"source product gross": {
"base": 69.83000000000004,
"high": 69.83000000000004,
"low": 69.83000000000004
}
},
"equipment_id": "R15-BOM-MV-OUTGOING-PANEL",
"ledger_id": "R15-MV-OUTGOING-PANEL-COUNT",
"physical_kg_per_unit": {
"base": 671.13,
"high": 671.13,
"low": 671.13
},
"quantity": 642,
"scope": "Comparable cubicle proxy; equipment-specific dimensions and exact ferrous split unresolved.",
"thermal_screen": null
},
{
"boundary": "B3",
"budget_residual_kg_per_unit": {
"source product gross": {
"base": 69.83000000000004,
"high": 69.83000000000004,
"low": 69.83000000000004
}
},
"equipment_id": "R15-BOM-MV-INCOMER-PANEL",
"ledger_id": "R15-MV-INCOMER-PANEL-COUNT",
"physical_kg_per_unit": {
"base": 671.13,
"high": 671.13,
"low": 671.13
},
"quantity": 24,
"scope": "Comparable cubicle proxy; equipment-specific dimensions and exact ferrous split unresolved.",
"thermal_screen": null
},
{
"boundary": "B3",
"budget_residual_kg_per_unit": {
"source product gross": {
"base": 69.83000000000004,
"high": 69.83000000000004,
"low": 69.83000000000004
}
},
"equipment_id": "R15-BOM-MV-TIE-PANEL",
"ledger_id": "R15-MV-TIE-PANEL-COUNT",
"physical_kg_per_unit": {
"base": 671.13,
"high": 671.13,
"low": 671.13
},
"quantity": 24,
"scope": "Comparable cubicle proxy; equipment-specific dimensions and exact ferrous split unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {
"source copper rail assembly": {
"base": 127.93582800000001,
"high": 127.93582800000001,
"low": 127.93582800000001
}
},
"equipment_id": "R15-BOM-BUSWAY",
"ledger_id": "R15-BUSWAY-COUNT",
"physical_kg_per_unit": {
"base": 172.06417199999999,
"high": 172.06417199999999,
"low": 172.06417199999999
},
"quantity": 3424,
"scope": "Only four-pole rail conductors; catalog gross and residual supplied as reference budget.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {
"selected net nonbattery mass": {
"base": 3677.4082399999998,
"high": 3287.955575,
"low": 3986.7687
}
},
"equipment_id": "R15-BOM-IT-UPS",
"ledger_id": "R15-IT-UPS-COUNT",
"physical_kg_per_unit": {
"base": 1032.59176,
"high": 1422.044425,
"low": 723.2313
},
"quantity": 856,
"scope": "Transformer-free rectifier/inverter/bypass assembly with external batteries and feeder paths excluded; semiconductors, windings not modeled here, fans and capacitors residual.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-FAC-UPS",
"ledger_id": "R15-FAC-UPS-COUNT",
"physical_kg_per_unit": {
"base": 362.52434,
"high": 499.69716875,
"low": 253.65232500000002
},
"quantity": 214,
"scope": "Transformer-free rectifier/inverter/bypass assembly with external batteries and feeder paths excluded; semiconductors, windings not modeled here, fans and capacitors residual.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-IT-MSB",
"ledger_id": "R15-IT-MSB-COUNT",
"physical_kg_per_unit": {
"base": 715.76,
"high": 1103.784,
"low": 448.29599999999994
},
"quantity": 428,
"scope": "Formed panel/enclosure and length of equivalent internal bare bus only; controls and switching hardware unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-FAC-MSB",
"ledger_id": "R15-FAC-MSB-COUNT",
"physical_kg_per_unit": {
"base": 548.2175,
"high": 852.8190000000002,
"low": 340.23749999999995
},
"quantity": 214,
"scope": "Formed panel/enclosure and length of equivalent internal bare bus only; controls and switching hardware unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-STS",
"ledger_id": "R15-STS-COUNT",
"physical_kg_per_unit": {
"base": 228.27165,
"high": 356.3118,
"low": 143.68128
},
"quantity": 1712,
"scope": "Formed panel/enclosure and length of equivalent internal bare bus only; controls and switching hardware unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-CRITICAL-COOLING-STS",
"ledger_id": "R15-CRITICAL-COOLING-STS-COUNT",
"physical_kg_per_unit": {
"base": 141.46865,
"high": 220.57908000000003,
"low": 89.03111999999999
},
"quantity": 107,
"scope": "Formed panel/enclosure and length of equivalent internal bare bus only; controls and switching hardware unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-CRITICAL-COOLING-PANEL",
"ledger_id": "R15-CRITICAL-COOLING-PANEL-COUNT",
"physical_kg_per_unit": {
"base": 153.99492,
"high": 240.14246399999996,
"low": 97.247646
},
"quantity": 107,
"scope": "Formed panel/enclosure and length of equivalent internal bare bus only; controls and switching hardware unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-MECHANICAL-ATS-PANEL",
"ledger_id": "R15-MECHANICAL-ATS-PANEL-COUNT",
"physical_kg_per_unit": {
"base": 563.9175,
"high": 877.3109999999999,
"low": 350.24625
},
"quantity": 107,
"scope": "Formed panel/enclosure and length of equivalent internal bare bus only; controls and switching hardware unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-EXTRA-IT-PANEL",
"ledger_id": "R15-EXTRA-IT-PANEL-COUNT",
"physical_kg_per_unit": {
"base": 33.106880000000004,
"high": 51.67233600000001,
"low": 20.956283999999997
},
"quantity": 856,
"scope": "Formed panel/enclosure and length of equivalent internal bare bus only; controls and switching hardware unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-ATC-ASSEMBLY",
"ledger_id": "R15-ATC-ASSEMBLY-COUNT",
"physical_kg_per_unit": {
"base": 66.0004,
"high": 103.08864000000001,
"low": 41.741879999999995
},
"quantity": 642,
"scope": "Formed panel/enclosure and length of equivalent internal bare bus only; controls and switching hardware unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-COOLING-CONTROL-PANEL",
"ledger_id": "R15-COOLING-CONTROL-PANEL-COUNT",
"physical_kg_per_unit": {
"base": 48.56685,
"high": 75.940308,
"low": 30.847685999999996
},
"quantity": 107,
"scope": "Formed panel/enclosure and length of equivalent internal bare bus only; controls and switching hardware unresolved.",
"thermal_screen": null
},
{
"boundary": "B3",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-SUBSTATION-PROTECTION-CONTROL",
"ledger_id": "R15-SUBSTATION-PROTECTION-CONTROL-COUNT",
"physical_kg_per_unit": {
"base": 286.6005,
"high": 447.25679999999994,
"low": 182.2911
},
"quantity": 6,
"scope": "Formed panel/enclosure and length of equivalent internal bare bus only; controls and switching hardware unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-SHELF-TAP-WHIP",
"ledger_id": "R15-SHELF-TAP-WHIP-COUNT",
"physical_kg_per_unit": {
"base": 1.9154393999999997,
"high": 2.490978,
"low": 1.2873609
},
"quantity": 54784,
"scope": "Three bare phase wires and one smaller protective-earth allowance per 3 m electrified shelf whip. Source length follows frozen total and count.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R4-FEEDER-IT-RECTIFIER",
"ledger_id": "R15-IT-UPS-COUNT",
"physical_kg_per_unit": {
"base": 1792.823613658,
"high": 4019.7682000475997,
"low": 703.3919454632
},
"quantity": 856,
"scope": "MSB to rectifier/common-input branch. Phase and protective-earth conductors, plus steel support outside equipment. No cable insulation or termination inventory.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R4-FEEDER-IT-BYPASS",
"ledger_id": "R15-IT-UPS-COUNT",
"physical_kg_per_unit": {
"base": 636.0461147803001,
"high": 1299.5672295606,
"low": 248.92344591211997
},
"quantity": 856,
"scope": "Local bypass branch after common-input split only. Phase and protective-earth conductors, plus steel support outside equipment. No cable insulation or termination inventory.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R4-FEEDER-IT-OUTPUT",
"ledger_id": "R15-IT-UPS-COUNT",
"physical_kg_per_unit": {
"base": 2226.16140173105,
"high": 4873.377110852251,
"low": 1120.15550660454
},
"quantity": 856,
"scope": "UPS output to downstream distribution, separate circuit. Phase and protective-earth conductors, plus steel support outside equipment. No cable insulation or termination inventory.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R4-FEEDER-IT-XFMR",
"ledger_id": "R15-IT-XFMR-COUNT",
"physical_kg_per_unit": {
"base": 3371.5570000000007,
"high": 6130.621350000001,
"low": 1601.86236
},
"quantity": 428,
"scope": "IT stepdown secondary to main switchboard; external low-voltage route. Phase and protective-earth conductors, plus steel support outside equipment. No cable insulation or termination inventory.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R4-FEEDER-FAC-XFMR",
"ledger_id": "R15-FAC-XFMR-COUNT",
"physical_kg_per_unit": {
"base": 2028.18616,
"high": 4210.381350000001,
"low": 1089.79836
},
"quantity": 214,
"scope": "Facility transformer secondary to main switchboard; external low-voltage route. Phase and protective-earth conductors, plus steel support outside equipment. No cable insulation or termination inventory.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R4-FEEDER-PDU",
"ledger_id": "R15-PDU-COUNT",
"physical_kg_per_unit": {
"base": 392.13120000000004,
"high": 767.0384999999999,
"low": 187.5876
},
"quantity": 1712,
"scope": "STS downstream branch to consolidated PDU primary. Phase and protective-earth conductors, plus steel support outside equipment. No cable insulation or termination inventory.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R4-FEEDER-FAC-UPS-IN",
"ledger_id": "R15-FAC-UPS-COUNT",
"physical_kg_per_unit": {
"base": 277.7596,
"high": 596.5855,
"low": 125.05839999999999
},
"quantity": 214,
"scope": "Facility main switchboard to separate UPS input; assumed input apparent-power margin. Phase and protective-earth conductors, plus steel support outside equipment. No cable insulation or termination inventory.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R4-FEEDER-FAC-UPS-OUT",
"ledger_id": "R15-FAC-UPS-COUNT",
"physical_kg_per_unit": {
"base": 375.7924,
"high": 715.9026,
"low": 156.323
},
"quantity": 214,
"scope": "Facility UPS output to protected cooling distribution. Phase and protective-earth conductors, plus steel support outside equipment. No cable insulation or termination inventory.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R4-FEEDER-CHILLER",
"ledger_id": "R15-AIR-COOLED-CHILLER-COUNT",
"physical_kg_per_unit": {
"base": 491.39840000000004,
"high": 974.3595,
"low": 208.41228
},
"quantity": 1070,
"scope": "Mechanical ATS distribution to selected 460 V class chiller. Allows 405 kW plus assumed power-factor and starting margin for copper geometry. Phase and protective-earth conductors, plus steel support outside equipment. No cable insulation or termination inventory.",
"thermal_screen": null
},
{
"boundary": "B3",
"budget_residual_kg_per_unit": {},
"equipment_id": "R4-FEEDER-GENERATOR",
"ledger_id": "R15-STANDBY-GENERATOR-COUNT",
"physical_kg_per_unit": {
"base": 6743.114000000001,
"high": 12942.42285,
"low": 2402.79354
},
"quantity": 642,
"scope": "Standby output to service transfer gear; distinct from utility transformer circuits. Phase and protective-earth conductors, plus steel support outside equipment. No cable insulation or termination inventory.",
"thermal_screen": null
},
{
"boundary": "B3",
"budget_residual_kg_per_unit": {},
"equipment_id": "R4-FEEDER-MV-CAMPUS",
"ledger_id": "R15-MV-OUTGOING-PANEL-COUNT",
"physical_kg_per_unit": {
"base": 940.09392,
"high": 2015.9429599999999,
"low": 406.46196000000003
},
"quantity": 642,
"scope": "One 34.5 kV outgoing circuit per panel, onward to IT or facility stepdown transformer. Phase and protective-earth conductors, plus steel support outside equipment. No cable insulation or termination inventory.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {
"cabinet non-population envelope": {
"base": 56.28344,
"high": 21.604209999999995,
"low": 89.13385
},
"module-associated population envelope": {
"base": 135.7394602366864,
"high": 77.36942602166584,
"low": 170.27720528799438
},
"whole 18-module cabinet": {
"base": 192.02290023668638,
"high": 89.97363602166587,
"low": 268.4110552879944
}
},
"equipment_id": "R15-BOM-IT-BATTERY",
"ledger_id": "R15-IT-BATTERY-COUNT",
"physical_kg_per_unit": {
"base": 397.9770997633136,
"high": 500.02636397833413,
"low": 321.5889447120056
},
"quantity": 7704,
"scope": "Nested cells, module-associated hardware and cabinet; gross mass not booked. Electronics and material residual retained.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {
"cabinet non-population envelope": {
"base": 56.28344,
"high": 21.604209999999995,
"low": 89.13385
},
"module-associated population envelope": {
"base": 135.7394602366864,
"high": 77.36942602166584,
"low": 170.27720528799438
},
"whole 18-module cabinet": {
"base": 192.02290023668638,
"high": 89.97363602166587,
"low": 268.4110552879944
}
},
"equipment_id": "R15-BOM-FAC-BATTERY",
"ledger_id": "R15-FAC-BATTERY-COUNT",
"physical_kg_per_unit": {
"base": 397.9770997633136,
"high": 500.02636397833413,
"low": 321.5889447120056
},
"quantity": 642,
"scope": "Nested cells, module-associated hardware and cabinet; gross mass not booked. Electronics and material residual retained.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {
"legacy dry chiller proxy, metals only": {
"base": 5963.1066983480105,
"high": 1612.8053862925517,
"low": 9012.408354695073
}
},
"equipment_id": "R15-BOM-AIR-COOLED-CHILLER",
"ledger_id": "R15-AIR-COOLED-CHILLER-COUNT",
"physical_kg_per_unit": {
"base": 7146.8933016519895,
"high": 11497.194613707448,
"low": 4097.591645304927
},
"quantity": 1070,
"scope": "AFC direct-freecooling chiller: separate external coils, internal evaporator, compressor castings, fans and chassis. Net mass proxy used for metals only. Operating fluids other than refrigerant unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R4-CHILLER-REFRIGERANT",
"ledger_id": "R15-AIR-COOLED-CHILLER-COUNT",
"physical_kg_per_unit": {
"base": 169.0,
"high": 169.0,
"low": 169.0
},
"quantity": 1070,
"scope": "One initial R513A equipment charge per FH3145. Separate from dry chiller proxy.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-WARM-WATER-CRAH",
"ledger_id": "R15-WARM-WATER-CRAH-COUNT",
"physical_kg_per_unit": {
"base": 567.8525457088973,
"high": 914.8593659624553,
"low": 347.3101846242164
},
"quantity": 2140,
"scope": "Steel frame, copper tube/Al fin coil, stainless drain tray and fan assembly. Reduced water and air-side thermal screen only; coil pressure drop, glycol properties and fan duties remain unqualified.",
"thermal_screen": {
"lower_order_UA_kW_K": {
"base": 45.745532595342105,
"high": 57.708518267236485,
"low": 37.55414333339293
},
"required_UA_kW_K": 33.66
}
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {
"preliminary wet reference gross": {
"base": 853.45486676939,
"high": 87.22886272900382,
"low": 1301.4676595331225
}
},
"equipment_id": "R15-BOM-CDU",
"ledger_id": "R15-CDU-COUNT",
"physical_kg_per_unit": {
"base": 939.54513323061,
"high": 1705.7711372709962,
"low": 491.5323404668776
},
"quantity": 856,
"scope": "Internal stainless exchanger and pipes, pumps and controls cabinet. Fluid remains part of budget residual, not assigned as metal.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-PRIMARY-PUMP",
"ledger_id": "R15-PRIMARY-PUMP-COUNT",
"physical_kg_per_unit": {
"base": 326.351,
"high": 518.87,
"low": 193.632
},
"quantity": 428,
"scope": "45 kW class pump, motor and skid. Component volumes are allowances. No scaling from nominal kW.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-PRIMARY-PIPE-RUN",
"ledger_id": "R15-PRIMARY-PIPE-RUN-COUNT",
"physical_kg_per_unit": {
"base": 54657.96220339313,
"high": 58643.6064672583,
"low": 50834.83329404677
},
"quantity": 214,
"scope": "No doubling of already combined supply and return routes. External straight pipe and initial fluid only; valves, insulation, bends and fittings unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-SECONDARY-PIPE-RUN",
"ledger_id": "R15-SECONDARY-PIPE-RUN-COUNT",
"physical_kg_per_unit": {
"base": 1916.2032314253026,
"high": 2035.3975736270816,
"low": 1782.128908407392
},
"quantity": 856,
"scope": "No doubling of already combined supply and return routes. External straight pipe and initial fluid only; valves, insulation, bends and fittings unresolved.",
"thermal_screen": null
},
{
"boundary": "B2",
"budget_residual_kg_per_unit": {},
"equipment_id": "R15-BOM-STRATIFIED-BUFFER-TANK",
"ledger_id": "R15-STRATIFIED-BUFFER-TANK-COUNT",
"physical_kg_per_unit": {
"base": 56373.02943947113,
"high": 58747.18491353018,
"low": 54623.592456765095
},
"quantity": 214,
"scope": "Closed 50 m³ buffer vessel with equivalent cylindrical shell and full design initial fluid volume; no structural pad or thermal insulation.",
"thermal_screen": null
},
{
"boundary": "B3",
"budget_residual_kg_per_unit": {
"C175 power-family dry proxy": {
"base": 10602.75,
"high": 4102.399999999998,
"low": 15364.75
},
"twenty matched-family assembled head proxies": {
"base": 424.0,
"high": 251.19999999999982,
"low": 640.0
}
},
"equipment_id": "R15-BOM-STANDBY-GENERATOR",
"ledger_id": "R15-STANDBY-GENERATOR-COUNT",
"physical_kg_per_unit": {
"base": 14397.25,
"high": 20897.600000000002,
"low": 9635.25
},
"quantity": 642,
"scope": "Dry metal subassemblies for open-skid generator package. Standby feeder, external fuel equipment and fuel excluded. Gross balance is an unallocated residual.",
"thermal_screen": null
}
]
}
Source details
Run 04 research. Equipment material estimates with documented assumptions and scope. Web prose uses current site terminology; downloadable records preserve original wording. Hashes identify the downloadable records.
Source: build/run04/coverage.json
SHA-256: 54622628d2ea58c7d176764a544ec91d15b31f2b8be7b927b3b6aa82949c5721
Download research file
Optional: tell Sid you’re reading
The document is open; sharing your name/email is optional.