# Mass Balance of Intelligence: Run 02 findings

Snapshot `SNAP-RUN02` · evidence access date 7 October 2026 · fixed object
`PLANT-GB300-1GW-2026Q4-A` · unchanged compute configuration
`CFG-GB300-2026Q4`.

**The first plant-specific material balance remains OPEN. Qualified copper,
aluminum and steel subtotals are null at every boundary.** Run 02 establishes
180.83 tonnes of R513A refrigerant in the selected B2 chillers, records selected
equipment masses with unresolved composition, and preserves explicitly qualified
gross-mass proxies and construction alternatives separately. The public evidence
does not support total plant mass, total copper required, or a material
completeness percentage.

This is a result about the specified reference design. It is not an observed
procurement inventory or a universal material intensity for 1 GW AI facilities.
The auditable calculation is installed design count × material kg per selected
equipment unit. Its [machine-readable balance](build/run02/material_balance.json),
[equipment reconciliation](build/run02/material_reconciliation.md) and
[CSV reconciliation](build/run02/material_reconciliation.csv) expose admitted
coefficients, explicit unknowns, source terminology, product matching, boundary
and lineage.

## Preserved reference plant and preflight

The latest upstream Run 01.5 repository, commit
`15155a6dbddc18afe3e4ae55f1c561d8269daa99`, was inspected before material work.
README, Accounting Standard v0.1, previous findings, the equipment BOM,
standard changelog, unknowns, design decisions, sensitivities and canonical
tables were read. All **146 inherited tests** passed. The final Run 01.5 BOM
reproduced byte-for-byte in JSON, CSV and Markdown. The
[preflight register](research/run02/baseline/preflight.json) and generated
[preservation checks](build/run02/preservation.json) retain the evidence.

The repository's final design governs exact counts. In particular it contains
**642 module stepdown transformers** (428 IT and 214 facility), **856 CDUs**,
**2,140 CRAHs** and **1,070 chillers**. These differ from the approximate counts
in the Run 02 brief. The design remains 107 complete modules, six campus
substations, 24 × 84 MVA campus transformers, 856 IT UPS units, 214 facility UPS
units, 1,712 transformer PDUs, 1,712 IT STS units, 428 external pumps,
214 × 50 m³ tanks, 642 generators and 8,346 Li5 battery cabinets.

The denominator remains exactly **1 GW normalized commissioned IT**. Installed
IT capacity is **1.009178947368421 GW**, and normalized compute inventory remains
6,785.714286 GB300 rack equivalents, 488,571.428571 B300 accelerators and
244,285.714286 Grace CPUs. Rack equivalents are a normalized design inventory,
not purchased integer racks. No compute configuration, selected equipment,
thermal architecture or plant count was replaced. Accounting Standard v0.1 and
historical source, claim, ledger, design and snapshot records remain intact.

## Quantified materials by boundary

All entries below are **quantified portions**, rather than complete physical
stocks. `UNKNOWN` represents null. Missing scope does not contribute an
assumed zero.

| Material | B1 | B2 incremental | B2 cumulative quantified portion | B3 incremental modeled | B3 cumulative quantified portion |
| --- | ---: | ---: | ---: | ---: | ---: |
| Elemental copper | UNKNOWN | UNKNOWN | UNKNOWN | UNKNOWN | UNKNOWN |
| Elemental aluminum | UNKNOWN | UNKNOWN | UNKNOWN | UNKNOWN | UNKNOWN |
| Steel | UNKNOWN | UNKNOWN | UNKNOWN | UNKNOWN | UNKNOWN |
| R513A refrigerant blend | UNKNOWN | 180.83 t | 180.83 t | UNKNOWN | 180.83 t |

The R513A cumulative values carry forward the enumerated B2 stock. They do not
claim that unknown B1 or B3 stock equals zero, or that the complete cumulative
boundary has closed. [Boundary subtotals](build/run02/boundary_subtotals.csv)
retain unresolved scopes and `is_total=false`. Cumulative B2 adds B1 and
incremental B2; cumulative B3 additionally adds incremental modeled B3.
Cumulative values are never added to one another.

The qualified refrigerant calculation is:

`1,070 selected FH3145 chillers × (89 + 80) kg R513A/chiller = 180,830 kg`.

Vertiv's captured [SL-70790 installer guide](research/run02/cooling/afc-installer-sl70790.pdf),
printed p53, Table 7.1, declares the two separate circuit charges. The guide's
model decoding identifies the selected direct-free-cooling FH3 145 product and
R513A blend. Although Run 01.5 selected FH3145 as a functional alternative to
RD030's FF3145, this charge is exact evidence for the **selected FH3145**;
no charge is transferred to FF3145. The subtotal is **DESIGN-QUALIFIED**:
selected design count, exact selected product coefficient, reproducible
multiplication and clear material/boundary. It does not assert measured
commissioned charge or acceptance of every installation interface.

The subtotal is **180.83 tonnes / GW IT** and approximately **179.185 tonnes /
GW installed IT**. Allocating it across normalized compute racks gives
approximately **26.65 kg/rack equivalent of facility refrigerant**; that stock
is in chillers, not inside compute racks. All currently quantified R513A comes
from this one equipment class. Its 100% contribution share describes the
quantified R513A subtotal only. Copper, aluminum and steel contributor shares,
top-five/top-ten concentrations and intensities remain unavailable.

## Equipment mass with unresolved material composition

Gross equipment evidence is useful, but it cannot be relabeled as copper,
steel, battery active material or a complete plant mass. The
[gross inventory](build/run02/gross_equipment_inventory.json) separates selected
equipment evidence from conditional proxies.

| Incremental scope / equipment | Calculation | Gross mass | Evidence use and limitation |
| --- | --- | ---: | --- |
| B2 IT UPS | 856 × 4,710 kg | 4,031.760 t | Selected 2 MW UL 480 V product; batteries separate; composition unresolved |
| B2 IT STS | 1,712 × 2,177 kg | 3,727.024 t | Selected LayerZero 1,600 A product; composition unresolved |
| B2 critical-cooling STS | 107 × 975 kg | 104.325 t | Selected LayerZero 800 A product; composition unresolved |
| B2 selected electrical subtotal | Three disjoint rows above | 7,863.109 t | Scoped gross equipment subtotal |
| B2 IT/facility battery cabinets | (7,704 + 642) × 590 kg | 4,924.140 t | Selected 18-module Li5 cabinet gross; chemistry is LFP, constituent masses unresolved |
| B2 selected gross subtotal | Electrical plus battery cabinets | **12,787.249 t** | Known selected gross equipment for these classes only |
| B1 coldplate assemblies | Preserved Run 01.5 rack equivalents × 18 × 9.5 kg | **1,160.357143 t** | Tier 3 PROXY; population/function match, selected installation unqualified |
| B3 standby generators | 642 × 25,000 kg | **16,050 t** | Tier 3 dry gross-mass PROXY; published power-family voltage differs from selected 480 V class |

The B1 count is derived from the **plant-linked preserved Run 01.5 rack
quantity**, multiplied by 18 trays/rack. It does not substitute a differently
scoped historical count for the plant lineage. LITEON's
[GB300 coldplate sheet](research/run02/compute/captures/liteon_gb300_coldplates.pdf)
reports a 9.5 kg module for four Blackwell Ultra GPUs and two Grace CPUs,
matching device population and 1,400 W GPU thermal rating. It includes tubing
and connectors. Its stated 2U chassis suitability differs from the selected
1U Supermicro tray; actual mounting, routing and dry/wet mass are unqualified.
Low/high transfer bounds remain null. It is a conditional assembly proxy,
not a copper coefficient or known exact-target mass.

The generator proxy excludes operating fluids, fuel stock and separately
modeled fuel systems. The three boundary gross values above do not form a
complete plant denominator. Their missing equipment and product mismatches
prevent a material closure calculation. Gross equipment and nested component
or material views must never be added together.

## What the workstreams established

**B1 compute.** Exact rack/tray, frame, GPU/CPU/HBM, NVLink, NIC, shelf/PSU,
busbar, cable, coldplate/manifold and PCB evidence was investigated. Public
OEM carbon-footprint summaries disclose some product weights and internally
collected material data, but their emissions bars are not material-mass
fractions. Same-platform Lenovo weights, Supermicro MGX frame-family masses,
the OCP 31 kg busbar assembly and measured A100 teardown remain context with
explicit mismatch records. The GB300-labelled Supermicro 22 kg sheet describes
an incompatible two-GPU/test-board configuration and is excluded. See the
[B1 evidence handoff](research/run02/compute/HANDOFF.md).

The 977,142.857143 embedded GPU logic dies remain a nested component count.
Physical silicon mass needs qualified area, post-thinning thickness and disjoint
logic/HBM/interposer/package scope. No semiconductor mass is inferred from
memory GB, transistor count, generic wafer thickness, fabrication yield or
wafer starts. The manufacturing questions remain for a later run.

**Electrical infrastructure.** Exact selected UPS/STS weights are retained.
Transformer, alternator, busway and UPS material declarations were located, but
unselected winding conductors, voltage/topology differences, incomplete
manufacturing-model boundaries or inconsistent packaging denominators prevent
qualified Cu/Al/steel transfers. Family checks do not establish a universal
kg/MVA or kg/A law. Complete campus substations overlap their separately modeled
transformers, panels and protection and receive no additive umbrella coefficient.
See [electrical candidates](research/run02/electrical/proposed_coefficients.json)
and the [transformer handoff](research/run02/transformers/HANDOFF.md).

**Cooling infrastructure.** Selected dry/air-cooled heat rejection remains fixed.
Schneider chiller/CRAH declarations, a Carrier CDU declaration and stainless
tank alternatives are retained with rating, cooling, material and configuration
mismatches. LCIA extrapolation factors do not establish material extrapolation
factors. Copper, aluminum, steel and stainless steel in the selected cooling
equipment remain unresolved. Newer FH3145 family dry/static/operating weights
have different definitions and do not resolve coolant inventory by subtraction.
See the [cooling handoff](research/run02/cooling/HANDOFF.md).

**Batteries.** The design already selected Li5 LFP: 8,346 cabinets, 150,228 nested
modules and 259.5606 MWh nominal DC energy. Chemistry does not provide element
coefficients. A same-family seismic certificate's 53 lb module gives an isolated
Tier 2 assembly partition scenario of **3,611.540552 t modules** and
**1,312.599448 t non-module residual**, reconciling to 4,924.14 t cabinet gross.
The certified and current cabinet versions differ, so transfer bounds remain
null. Neither the module mass nor residual is a selected elemental coefficient;
the residual includes conductors, controls and enclosure, not only steel. The
partition remains separate from headline material subtotals. See the
[battery handoff](research/run02/battery/handoff.md).

Lithium, nickel, cobalt, manganese, iron/phosphate-bearing materials, graphite,
copper, aluminum, polymers and electrolyte masses remain null where exact or
qualified coefficients are unavailable. LFP identity does not warrant setting
Ni/Co/Mn to zero across all module and cabinet components.

## Fluid capacity, inventory and annual water

The [fluid output](build/run02/fluid_inventory.json) reports **18,313.806876 m³
of nominal geometric capacity**: 10,700 m³ full tank volume, 6,807.045882 m³
primary straight-pipe capacity and 806.760993 m³ secondary straight-pipe
capacity. DN450/DN200 are the inherited hydraulic internal-diameter
approximations, not qualified manufactured bores. Fill, fittings, expansion
space, equipment internals and rack loops remain unresolved. This is not an
observed filled water inventory.

An isolated OEM EG30 recipe/density scenario converts this geometry into glycol
and water masses, but procurement has not qualified that exact weight-basis
recipe, inhibitor package, density or fill condition. Its solution parent is
not added to its glycol/water children. Annual whole-site water withdrawal,
consumption and makeup remain **null**. The selected architecture has no cooling
tower or adiabatic spray circuit; this scoped absence does not establish zero
whole-site water use.

## Coverage, uncertainty and external comparisons

[Structural coverage](build/run02/structural_coverage.csv) identifies admitted
material classes and unresolved equipment, rather than inventing a material
completeness denominator. The principal missing decompositions are rack
internals; both transformer layers; switchboards, PDUs and facility conductors;
battery cells/enclosures; cooling equipment/piping; generators and their fuel
systems. Device inventories for external IT remain unqualified. Buildings,
foundations and other unspecified civil/site scope are not closed by the
equipment BOM. Shared grid generation/transmission, generic upstream
manufacturing, mines and refineries are outside the current modeled B3 scope.

Low/base/high follow published points, genuine coefficient uncertainty and
qualified transfer limits. Unavailable endpoints remain null. The refrigerant
169/169/169 kg declaration represents an OEM point, not zero physical uncertainty.
No arbitrary percentage band, statistical confidence interval or missing-scope
uplift is applied. [Uncertainty method](docs/RUN_02_UNCERTAINTY.md) explains
propagation, component overlap and isolated alternatives.

External copper and grid estimates are researched after bottom-up reconciliation
and retained as benchmarks with their capacity denominator, boundary, vintage,
geography and stock/flow semantics. They do not supply plant coefficients. With
the plant copper subtotal unresolved, a numerical plant-versus-benchmark gap or
error cannot be asserted. A broad benchmark cannot fill the missing denominator.
See the [benchmark reconciliation](research/run02/benchmarks/benchmark_reconciliation.md) and [evidence captures](research/run02/benchmarks/capture_manifest.json).

No ore requirement or extraction allocation is calculated. Recycled-content or
manufacturing-input declarations, where encountered, retain their source basis
and do not silently change installed elemental stock.

## Reproduce and assess the result

```bash
python -m unittest discover -s tests -v
python scripts/reproduce.py
python scripts/reproduce_run015.py
python scripts/reproduce_run02.py
python -m mbi material-balance --plant PLANT-GB300-1GW-2026Q4-A --snapshot SNAP-RUN02
```

The inherited suite passed 146 tests; the integrated Run 02 suite passes
193 tests. Tests exercise material identity,
proxy gates, unresolved nulls, nested scope, incremental/cumulative arithmetic
and historical preservation. Internal consistency cannot supply missing physical
composition evidence.

The reproducer validates canonical records and local source hashes, preserves
historical entities and final Run 01.5 BOM bytes, rebuilds the SQLite query layer
and writes [audited artifacts](build/run02/manifest.json), including the
[provenance register](build/run02/provenance_register.json). Run 02 adds
first-class material-coefficient and plant-application records, source terms,
proxy qualification and `DESIGN-QUALIFIED` evidence use without revising the
governing standard. No automatic public publication or supplier messages occur.

The immediate evidence priorities are selected Supermicro rack/tray material
declarations, selected transformer winding/BOM specifications, exact voltage
UPS/STS and PDU declarations, current Li5 module/cell substance masses, and
selected chiller/CDU/CRAH/pump/piping decompositions. These are the gates to
closing the first copper, aluminum and steel balance.